Explosion-proof cable resistance thermometer
System E-KF-OV

These sensors are used in temperature measurement in systems for the approved “increased safety” type of protection in industrial systems, power plants, electrical machines, wind turbines, refrigeration and air conditioning technology and, above all, systems in the chemical industry.

Cable resistance thermometers are available in numerous configurations and  they can also be used in the narrowest parts of the system.

Installation lengths, diameters, sensor types, cable types, etc. can also be individually adapted to your operational system or product parts.

The cable end can be configured with different connection options (plug or mating plug) on request.

For inquiries, use our configurator or contact us directly.

Type E-KF-OV21A

Configure & Requests

Accuracy class according to IEC 60751

°C
DIN B
DIN A
(1/2 DIN B)
DIN AA
(1/3 DIN B)
1/10
DIN B
0
± 0,3K
± 0,15K
± 0,1K
± 0,03K
100
± 0,8K
± 0,35K
± 0,27K
± 0,1K
200
± 1,3K
± 0,55K
± 0,44K
± 0,17K